Reports /Compliance

Inspection history

TaskTargetEngineerPerformedResultNotes
Manual call point function testCall Point 104 · Warehouse Anandani25-08-2026 10:12:00passTriggered and reset without fault.
Gateway link & signal auditGW-046super01-08-2026 09:40:00advisorySignal 61%, recommend repeater.
Battery replacement checkHeat 103 · Main Doorsuper20-07-2026 15:05:00failBattery at 18%, replacement scheduled.
Smoke detector sensitivity testSmoke 101 · Kaizennandani02-06-2026 11:30:00passWithin tolerance.
Sounder audibility testSounder 201 · SCM 2nandani15-04-2026 14:00:00pass95 dB at 3m.

Device test coverage

DeviceTypeZoneLast testedNext dueStatus
Smoke 101smoke00100 · Kaizen02-06-202602-09-2026overdue
Smoke 102smoke00300 · Main Doornever tested
Heat 103heat00300 · Main Door20-07-202620-08-2026overdue
Call Point 104manual-call-point02900 · Warehouse A25-08-202625-11-2026in date
SCM 1scm04300 · SCM 1never tested
SCM 2scm04400 · SCM 2never tested
SCM 3scm04500 · SCM 3never tested
Sounder 201sounder04400 · SCM 215-04-202615-10-2026in date
Smoke 105smoke02900 · Warehouse Anever tested

Panel battery & power history

WhenPanel / gatewayEvent
05-09-2026 10:31:50GW-044Currently running on battery
01-09-2026 12:20:25GW-046Battery Power
01-09-2026 12:20:25GW-046Battery Power

Overdue maintenance summary

By target

  • Smoke 101 · Kaizen1
  • Heat 103 · Main Door1
  • GW-0461
  • Zone 04500 · SCM 31

By frequency

  • quarterly2
  • monthly2